| General
Acoustic Engineering for Yachts |
This section outlines those
items of concern in the design of a quiet vessel.
- Cavitation
and Propeller induced Vibration:
The propeller tip clearance should be a minimum
of 20% of the propeller diameter; for very
quiet vessels – a wake survey should
be taken and wake adapted propeller should
be designed; tip velocity should be held to
less than 105 fps; preferred that propeller
induced pressure pulses not exceed 1.1 psi
at blade freq. & 0.5 psi at twice blade
freq.
- Foundations:
Foundations are to be designed with due regard
for noise and vibration; dynamic stiffness
should by ten times the stiffness of isolation
mounted equipment; cantilever foundations
should be avoided; foundations should not
be placed on bulkheads adjacent to noise sensitive
compartments.
- Shaft
Struts:
Struts are to be V form and airfoil shaped
or faired to minimize resistance and cavitation.
- Acoustic
Insulation:
(See Separate design guidance below)
- HVAC:
Particular attention should be directed toward
designing and installing an HVAC system with
minimal airborne and structureborne sound
transmission (see separate design guidance).
High velocity systems (above 1500 fpm) should
be avoided.
- Vibration
and Noise Control Features:
All diesel generator sets, air compressors,
fans and blowers should be installed on resilient
mounts; select rotating equipment in lieu
of reciprocating equipment; utilize equipment
that vendors certify as having low noise and
vibration source levels.
- Combustion
Air Systems:
Each diesel engine is to be fitted with an
air filter/silencer. Ducts to weather are
to have either silencers or sound traps. Louvers
in hull sides are not to be adjacent to noise
sensitive compartments.
- Combustion
Exhaust Systems:
Each diesel engine is to be fitted with a
high attenuation (high Dynamic Insertion Loss
– DIL) silencer. Resilient mounting
of the exhaust system may be necessary to
meet the noise requirements.
Particular attention shall be given to the
arrangement of the ship service generator
resilient mounting system when selecting expansion
joints.

| Design
Guidance: Acoustic Insulation & Privacy |
Acoustic
Insulation: The following treatments
shall be provided as a minimum:
Key Points:
- To be considered ‘acoustic
insulation,’ the material must be the
finish surface. For instance, fiberglass insulation
placed between a structural bulkhead and a
joiner bulkhead is not considered acoustic
insulation (though it will help increase the
airborne transmission loss, not the absorption).
All acoustic material should have a Noise
Reduction Coefficient (NRC) of 0.75 or better.
Material vendors can provide this information.
- If the ‘acoustic
insulation’ is to be covered by a sheathing,
the sheathing must be perforated. Perforated
lining usually have 0.125 inch holes on staggered
center and must be painted prior to installation.
The builder should cover and protect perforated
linings during construction to assure that
the perforations are not plugged by paint
and debris. To obtain the chosen color, the
perforated sheathing should be anodized not
painted.
- Thermal or fire insulations,
if left as the finish surface, can also qualify
as acoustic insulation treatments.
- Ceilings panels, it used,
shall have sufficient suspension attachments
to preclude any sagging, vibration or buckling.
All continuous ceiling systems shall have
modules with perforations of 1.8mm holes on
3.5 mm centers. All units shall have an inlay
of 25mm or greater fiberglass or mineral wool.
Privacy
- If privacy is a concern
each stateroom and cabin should be sound insulated
for privacy along all boundary bulkheads.
An acceptable design standard for privacy
is an airborne sound insulation index (Ia)
of 30 dB. Joiner vendors should be made aware
of this requirement as soon as possible. Divisional
bulkhead should be continuous from deck to
deckhead. If no, curtain plates or limp mass
layers should be used between the top of the
joiner and the deckhead.
- To provide adequate privacy,
the construction needs to present a uniform
transmission loss from deck to deckhead and
side to side. To ensure privacy in critical
areas, penetrations of the bulkhead should
be minimized. If penetrations are required,
they should be grouped and sealed light tight.
Criteria for Acceptable Noise Levels
Table 1: Passenger Ships-Passenger Accomodations
For yachts intended for overnight crusing, the
rules for passenger ships are to apply.
| Noise Levels in db(A) |
cm=comfort rating
number |
| Location |
--------50m
below-------- |
| Passenger top grade cabin |
44 |
47 |
50 |
| Passenger cabins,
standard |
49 |
52 |
55 |
| Public Spaces |
55 |
58 |
62 |
| Open deck recreation |
65 |
65 |
70 |
|
Table 2: High Speed and Light Craft-Length above
and below 50m
| Noise Levels in db(A) |
cm=comfort rating
number |
| Location |
----50m
below---- |
----Above
50m---- |
| |
cm=1 |
cm=2 |
cm=3 |
cm=1 |
cm=2 |
cm=3 |
| Passenger localities |
65 |
70 |
75 |
60 |
65 |
68 |
| Nav. bridge |
60 |
60 |
65 |
60 |
60 |
65 |
| Service areas/shops |
68 |
73 |
73 |
65 |
65 |
71 |
|
Table 3: Levels specified for transit conditions
apply to yachts not intended for overnight crusing.
For yachts intended for overnight crusing, the
rules for passenger ships are to apply for he
transit condition.
| Noise Levels in db(A) |
cm=comfort rating
number |
| Location |
----In
Harbor---- |
----Transit---- |
| |
cm=1 |
cm=2 |
cm=3 |
cm=1 |
cm=2 |
cm=3 |
| Sleeping Room |
35 |
40 |
45 |
|
|
|
| Lounges |
40 |
45 |
50 |
53 |
58 |
62 |
| Outdoor recreation |
50 |
55 |
60 |
75 |
80 |
85 |
| Nav. bridge |
|
|
|
60 |
60 |
65 |
|

| Design
Guidance: HVAC System Design |
This section covers guidance
for heating ventilation and air conditioning
(HVAC) systems. These systems are of concern
for compartments with requirements below 60dB(A).
Particular attention should be directed toward
the design and installation of an HVAC system
with minimal airborne and structureborne sound
transmission.
Noise from HVAC in machinery
spaces is generally not a concern, because the
ambient machinery noise levels are higher than
those created by HVAC equipment.
These are general design rules
that can minimize noise generated by HVAC systems.
Noise generation in HVAC system occurs from
four sources:
- Fans and Blowers
- Flow Noise generated at
Branches
- Flow Noise generated at
Turns
- Flow Noise generated at
Diffusers
Noise from these sources can
be transmitted to compartments either down stream
or upstream of the fan. Noise is also transmitted
into or out of a compartment by exposed ducts.
This is called break-out and break-in noise.
General
recommendations are as follows:
Air flow velocities should
be kept as low as possible. A target for quiet
systems should be velocities no higher than
1,000 ft/min., and never exceed 3,000 ft/min.
Higher velocities require extensive treatment,
particularly near each diffuser terminal.
Attached is the recommended maximum airflow
velocity for various installations:
Duct
Type |
Noise
Rating in Compartment |
Max.
Airflow in Duct, fpm |
Square
Turn |
70
60
50 |
2400
1600
900 |
Radius
turn or Sq. w/ Short |
70 |
2900 |
| Vanes
|
70
60
50 |
2000
1000 |
Square
Turn, Long Vanes |
70
60
50 |
3200
2500
1200 |
Radius
w/ Vanes
|
70
60
50 |
3300
2700
1200 |
|
1. Fan inlet air flow
should be straight for at least three duct diameters.
Turns closer than three diameters cause air
flow turbulence that increase noise.
2. The fan discharge should be straight for
a distance of at least three major duct widths
to avoid turbulence. Noise will significantly
increase due to turbulence. Noise will significantly
increase due to turbulence from elbows too close
to the discharge (or inlet).
3. Five to ten diameters of straight duct is
required for turbulence to die out and flow
to equalize. If the air flow does not become
smooth before the next fitting or terminal device,
the flow noise generated in the next element
will increased. For high velocity systems, it
is critical that offsets or transitions near
the fan can be avoided.
4. Design the HVAC system so that fans operate
near peak efficiency. Fans that do not operate
near peak efficiency will have higher noise
levels than fans operating at peak efficiency.
5. All ventilation fans should be resiliently
mounted and all connections to the fan, including
ducting and electrical cables, should be flexible
and at least as effective as the vibration isolators.
6. It possible, fans should not be attached
to bulkheads, decks and overheads that form
the boundaries of noise sensitive spaces.
7. Square turns, mitered elbows and zero radius
elbows should generally be avoided. Transforming
sections should be symmetrical. Avoid using
abrupt changes in cross-section or duct turns.
Noise increase when expansion in a transition
section exceeds a 7° angle from the straight
ahead.
8. Where possible, use circular metallic ducts
instead of rectangular ducts. Circular ducts
are more effective in preventing "breakout
noise" from the duct walls than are rectangular
ducts. In addition, circular ducts attenuate
noise moving down the duct better than rectangular
ducts. Finally, low frequency rumble caused
by turbulence, is less likely to occur in circular
ducts than in square ducts because circular
ducts are usually more rigid.
9. To avoid cross-talk between rooms served
by the same duct system, provide duct layout
offsets and 90° lined turns.
10.The use of vane turns is advised when the
turn is within five duct diameters of a fan,
regular elbows with ample radii should be used
as they cause less pressure drop in the flow.
11. The area of the duct that engages a fan
should be at least equal to, if not greater
than, the active area of the fan. Also, fan
intakes should be kept symmetrical with respect
to the fan.
12. Acoustically treated plena should be used
to reduce noise created by the flow, especially
when outlet ports are near fans or other noise
sources. The plena should be designed so that
the inlet and outlet ports do not lineup. Also,
the plenum should be made as large as possible.
13. The inside of the ducts should be as smooth
as possible to avoid turbulent flow. Seams should
be faired and protruding objects avoided. Improperly
fitted gaskets and flax couplings should be
avoided as well. Leading edges of dampers, splitters
and deflectors should be rounded or folded back.
When using vaned or un-vaned elbows use the
following table values for straight length of
duct preceding and following the fitting.
Turn
Size (Degrees) |
Diameters
of Straight Duct |
30 |
2 |
45 |
3 |
| 60 |
4 |
90 |
5 |
|
14. Splitters should be located as far from
the terminal as possible. The flow rate over
the splitter should be as low as possible. The
noise generated by the splitter varies as the
sixth power of the flow rate. Thus, a doubling
of speed corresponds to a 18 dB increase in
noise. Orifices are preferred for balancing
of systems.
15. External lagging used as an acoustic treatment
is not in general satisfactory. Internally lined
duct, with one-inch or two-inch thick fiberglass,
should be used extensively for noise control.
16. Rat guards on flexible couplings should
not bridge the flexible coupling. The guard
should be rigidly attached to only one end of
the ductwork and folded back at the other end
providing a 1/4 inch gap.
17. Diffuser terminals should have a manufacturer’s
noise rating that is at least 10 dB lower than
the compartment’s noise criterion. Acoustical
treatment of all air mixing boxes should be
considered.
18 . Noise from HVAC systems should be designed
to be at least 5 dB below the compartment noise
specification so that when combined with other
noise sources the noise specification is not
exceeded.
References:
A Practical guide to Noise and Vibration Control
for HVAC Systems, ASHRAE Inc., 1991.

| Design
Guidance: Resilient Isolation Mounts and
Foundations |
The general rules below should
be followed when mounting equipment on isolation
mounts. Keeping these guidelines in mind will
result in a well-designed system with fewer
changes.
Design Parameters:
1. Resilient mounts must be
sized so that the resonant vertical natural
frequency of the mounted system is less than
one third (1/3) of the machine disturbing frequency.
The machine disturbing frequency is generally
equal to the machine’s rotational rate.
The rotation rate, expressed in rpm, is divided
by 60 to determine frequency in Hertz (Hz or
cycles per second). The calculation of the resonant
frequency is shown on Figure 1.
2. In sizing resilient mounts the total weight
on the mounts should include the machinery,
subbases (above the mounts), associated fluids,
and weight of piping carried by the mounts.
3. The resilient mounts should be located equidistant
from the isolated equipment’s center-of-gravity
(CG) in both horizontal planes. In many cases,
mounts are located equidistant from the machinery’s
center-of-geometry. This is only acceptable
if the CG coincides with the center-of-geometry.
4. It is preferable to locate resilient mounts
in the CG vertical plane. This is generally
not possible, and vertical distance from the
mounts to the CG should be minimized, as shown
in Figure 2.
5. Keep the isolation mounts to a reasonable
number. It is preferable to have fewer rather
than more mounts. Four is usually the minimum
number of mounts.
6. A minimum one-inch clearance envelope should
be maintained around the mounted equipment to
prevent the unit from striking adjacent ship
structure, adjacent machinery or other objects
during maximum deflection.
7. Resiliently mounted equipment should have
flexible hose, exhaust, and/or cable connections.
The preferred design for fluid systems is to
incorporate two flexible hoses in 90° “dogleg”
or “V” configuration. Double arch
piece flexible hose, with motions that match
the maximum possible excursions of the mounted
equipment without over stressing the attached
piping or components can also be utilized. Tie
rods on flexible hose should only be used as
limit stops and should be supplied with rubber
grommets to prevent metal-to-metal contact.
The first three pipe hangars should have resilient
elements. Electrical connections should be made
with generous service loops.
Resilient Mount Features
8. Spring type should have
limit stops. Limit stops should be inherent
in the isolator design. If not, external, adjustable-limit
stops will need to be designed into the system.
Spring mounts typically provide the low frequency
required of the mounts. Other mount types, i.e.,
rubber or rubber & spring may also prove
suitable, since they offer greater isolation
at the mid- to high- frequencies. There are
many suppliers of vibration isolation mounts.
As noted above, the mounts should be designed
to have captive elements (i.e., equipment does
not come loose if mount fails). Choose from
vendors who make mounts designed for marine
applications. US Navy type rubber mounts should
be considered along with commercial manufactures
of spring and spring/rubber marine mounts. Barry,
Lord, Shock-Tech, Metalastik, and Christie Grey
are several recommended manufacturers.
9. For applications in oily environments such
as the Engine Room, the resilient element should
be made of neoprene or nitrile rubber. Natural
rubber may be used if in a protective housing
is provided. Mounts used on hot equipment, such
as exhausts systems, shall be protected from
the direct radiation of heat, unless the mount
is rated to take the expected heat. Thermal
break material shall be installed between the
hot side and the mount to limit the mount temperature
to the manufacturer’s tolerance. Mounts
used in wet areas, where there is a possibility
for more than occasional immersion of the mount
in sea or bilge water, should be installed using
non-corrosive hardware.
10. The drawings should note the load direction
and orientation for the mounts.
11. Fasteners should follow directions of the
mount manufacturer.
12. For dynamic analysis, each mount vendor
should provide both the static and dynamic stiffness
of the isolation mount. Furthermore, the following
equipment information will need to be provided:
total dry and wet weight (including subbase
and attached equipment), location of center-of-gravity,
translational (NOT rotational) mass moments
of inertia of the equipment, and location of
mounting feet.
Resilient Pipe Hangers
13. Resilient pipe hangars
are necessary with the use of flexible connections.
14. Resilient pipe hangars must be attached
to heavy, rigid parts of the ship structure
for the isolation treatment to be most effective.
Pipe hangars must not be attached to plating
sections between stiffeners.
15. Resilient pipe hangers should be used for
first three hangars locations from a resiliently
mounted component.
16. Resilient pipe hangars should have a natural
frequency less than or equal tot hat of the
mounts supporting the machinery to which the
associated piping is connected.
17. Do NOT attach pipe hangars to a machinery
subbase or piping directly to rigid ship structure
without a rubber grommet isolator or pipe hangar.
Downstrea, of the pipe hangars, the piping should
be held in rubber lined supports attached to
structural frames.
Foundation/ Subbase Design
18. The foundations used for
vibration isolated equipment have a different
criterion from hard mounted equipment. As mentioned
in item 3, the foundation must be able to accommodate
mounts located at the center-of-gravity, not
at the center-of-geometry.
19. Local stiffeners should be added to points
where mounts attach to the foundation. This
should generally consist of gussets on either
side of the isolation mount. The goal is to
have local stiffness at least one hundred (100)
times the stiffness of the resilient mount.
A minimum acceptable ratio of local to mount
stiffness is ten (10). The local foundation
stiffness can be computed by empirical or finite
element analysis (FEA).
20. Built-up foundations should be anchored
to hull framing. Noisy equipment should be attached
to structures having high impedance such as
stiff bulkheads or hull frame-stringer intersections.
Foundations should he designed to stress structural
members in tension or compression, bending and
torsional stress being less desirable.
21. The foundation should accommodate shock
excursion of various appendages of the mounted
equipment, (such as oil pan, cantilevered motors,
etc.).
22. If a resiliently mounted machinery item
consists of the two or more components connected
by shafting, use of a common subbase under both
units should be considered as a means to provide
proper alignment. A subbase may also be used
when it is necessary to secure resilient mounts
at some position other than that of the mounting
feet provided with a machine. Subbases should
be rigid.
23. Cantilevered foundations should be avoided.
Foundations should not be attached to surfaces
that are common with noise sensitive spaces,
e.g., accommodations, offices, and passageways
in those areas.
Installation Details
24. Welding or flame cutting
near the mounts shall be finished prior to installation
of the mounts. A note to this effect should
be put on appropriate drawings.
25. The actual height of each isolator should
be measured before and after the mounts are
completely loaded. This determines the mount
deflection. Equal deflection indicates equal
loading. Deviations of greater than 15% from
equal loading should be investigated. The mount
should not be cooked by more than 5 degrees.
26. The mount height should be measured again
after ten days to determine the amount of creep.
27. The resilient elements should never be painted.
A note to this effect should be put on appropriate
drawings.
28. Located resilient mounts or pipe hangars
such that they can be inspected regularly without
having to remove structural work.
29. Provision should be made for periodic removal
and replacement of resilient mounts or pipe
hangars. The requirement should be reflected
in headroom space and lateral clearance.
Calculation
of Vertical Resonant (Natural) Frequency and
Requirements for Effective Isolation

Rack guards, if required,
should not impede the free motion of the flexible
connections. Care should be taken in their design
and installation to ensure there is no metal-to-metal
contact during maximum excursion of the equipment
under ship slamming conditions.
Where break-out noise (the
escape of noise from within the duct into the
noise-sensitive compartment) could adversely
affect a compartment’s airborne noise
level, special attention to the design of the
flex connection is required.
Flexible duct connections
shall not be used to correct for misalignment.
Duct work and resiliently mounted equipment
shall be aligned within 3 mm per 25 mm of flexible
duct length as a minimum.
Exhaust Piping
Resilient mounted exhaust
systems shall be connected to their prime movers
and between various parts of the system with
flexible metallic bellows connections, or if
water cooled, with a suitable rubber hose connection.
Metallic bellows shall be of small corrugations,
extremely flexible type such as Lo-Corr by Flexonics,
or equal. They shall be of sufficient length
to allow free motion of all resiliently-mounted
elements under all ship conditions.
Particular care shall be exercised
in the location of the bellows and the resilient
supports of the system and system design to
prevent the imposing of undue loads and torques
on the bellows pieces due to ship motion and
thermal loads. The first flexible joint should
be located at the exhaust flange. These flex
bellows shall, as a minimum, have a life expectancy
of 10 years.
Insulation in the way of bellows
pieces shall be prevented from filing or jamming
the corrugations.
Exhaust systems should be
mounted resiliently to rigid ship structure,
not to plates between stiffeners. Care should
be taken to ensure that the exhaust system does
not resonate and that the proper loads are placed
on the mounts.
Flexible Wiring Connections:
As with piping and ductwork,
wiring to resiliently-mounted equipment must
be arranged in such a manner as to not restrain
the equipment under any ship’s motion.
Wiring shall run in a 90 degree or Z configuration
with a minimum free length of 30 cm for outside
diameters of up to 20 mm, 60 mm for diameters
from 20 mm to 40 mm and 1 m for diameters greater
than 40 ,,. At least 75 mm of slack should be
provided to allow for motion of the equipment
under ship slamming.
Flexible Shaft Couplings:
Selection of proper coupling
is determined by load carried by the shaft,
by the angular and parallel misalignment that
must be anticipated, and by the variation in
the axial separation between the two coupled
shaft ends.
Reasonable standards for shaft balance, alignment,
and runout should be invoked. The engine/gearbox
manufacturer should supply guidance on these
limits.

| Design
Guidance: Flexible Connections |
Flex Hose:
- Flexible hose shall be
installed on all piping that crosses a resilient
mount interface. Synthetic reinforced flexible
hose should be used wherever system requirements
and regulatory bodies permit. The intent is
to use as compliant a hose as possible based
on system constraints. To obtain freedom of
motion in two planes, flexible hose shall
be installed wither in a dog leg or right
angle configuration. The free length (that
length of hose unconstrained by clamps, fittings,
nipples, spigots, etc.) shall be at least
equal to 18.0 cm plus 4 hose diameters for
each leg.
- While dog leg configurations
are preferred, single right angle hose configurations
are permissible provided they are at least
equal in length to the dog leg configuration
and the hose manufacturer’s minimum
bend ratio is not exceeded. Where space is
limited, a single or double arch type flex
hose may be substituted.
- Renewable and fittings
shall be used whenever possible. These fittings
shall be compatible with and similar to the
material requirements of the associated piping
system.
- The preferred installed
hose configuration is the dog leg in the vertical
plane with the elbow downward. Depending on
specific arrangement and hose design, configurations
with the elbow up may require resilient support
at the elbow. Horizontal configurations shall
have support at the elbow.
- Critical (low noise systems)
flex hose installations shall have a heavy
rigid pipe hanger support at the equipment
end of the configuration attached to the equipment
sub-base. For those systems that do not require
resilient pipe hangers, a similar support
shall be attached to the opposite side of
the hose and be firmly attached to a structural
frame. Resilient supports are to be attached
to frames and never plate structures.
- The use of a single length
of flex hose is permissible for gage lines
and shall be in a 90 degree, U or Z configuration.
- Where required by regulatory
bodies, flex hose shall have fire protection
sleaving. Loose fitting flexible add-on non-metallic
sleaving is the preferred method. When and
where solid sleaving is required, it shall
be arranged in such a manner as to not impede
the free motion of the equipment under ship
slamming conditions and shall not provide
the opportunity for a shorting path between
mounted equipment and ship structure.
- All hoses should be at
least one size larger than the piping to which
they are connected in order to match the inside
diameters as closely as possible.
Flexible Duct Connections:
- Resiliently mounted elements
within a ducted system shall be connected
to non-resilient parts of the system by flexible
duct connections.
- Ducts containing fans,
whether resiliently mounted or not, should
be flexibly connected to their associated
duct work. These flexible connections shall,
as a minimum have sufficient flexibility to
allow full and free motion of the duct under
all ship operating conditions. These connections
should be non-metallic where system requirements
allow.
Piping Systems:
- Gate/butterfly valves shall
not be used for throttling service. Velocity
limits are provided in a separate design document.
Flexible piping connections should be used
to connect machinery and equipment mounted
on resilient isolators. These shall consist
of an assembly of flexible elements designed
to absorb the maximum excursions of the mounted
equipment without over stressing the attached
piping or components to which the flex connections
are attached.
- Minimum pipe bend radii
are provided in this section. Design of piping
support hangers is also addressed. Piping
to resiliently mounted equipment shall be
supported by means of resiliently mounted
pipe hangers.
- There shall be at least
two resilient mounts in a "V" configuration
with suspension such that each mount will
be loaded along its axis and will provide
total pipe support.
- Flexible connections shall
not be used to compensate for misaligned piping
or carry the weight of attached piping. Documentation
should be required of the piping hanger calculations.

| Design
Guidance: Equipment, Misc. |
Navigation Equipment:
- Navigation equipment located
within the Pilothouse and Radio Room -particularly
transformers, gyro repeaters-should be purchased
to a noise criteria that is 10 dB below the
compartment criterion. If possible, locate
transformers and gyro repeaters outside pilothouse.
- Cooling fans for racks
should be back mounted.
Galley/Scullery
- Refrigeration, dishwasher,
ice makers, and other noisy equipment located
within galley/scullery areas should be purchased
to a noise criteria that is 10 dB below the
compartment criterion. If make and model is
specified by the owner, he should provide
acoustic data.
- Small food processing appliances
are exempted from noise limits.
Windows:
- The windows panes should
always be mounted in rubber lined channels.
The rubber should be a minimum of ½"
thick of 30 to 40 durometer.
- To meet stringent noise
requirements, double pane windows may be required.
High Transmission Loss Constructions:
- Penetrations of bulkheads
between machinery spaces and noise sensitive
spaces should be minimized and grouped.
- All gaps at penetrations
should be sealed to be gas tight.
Copyright ® NCE 1997 Licensed
to Marine Sound Control
|
 |
|
 |
| Choose
ADE: |
1.Client-Focused
2.Total Service
3.High Quality
4.Innovation
5.Team Approach
| Results
in: |
On-time
project completion.
Innovative, functional, cost-effective
products and solutions. |
|
|
|